We are trying to size a control valve to feed an heat exchanger. The inlet pressure is 100 psig for a flowrate estimated at 195 lb/hr. What is the rule or how can I figure the dP across the valve? From what I understand, the steam trap will keep the pressure in the heat exchanger. Should I size the control valve with a dP of 2 psig?
You'll pick the delta-P across the control valve. The higher the
pressure drop that you can take, the smaller the valve can be. You're
dealing with a very small flow anyway, though.
A steam trap is
just an automatic valve. It'll open when it senses air or water, and
close when it senses steam. I'm assuming that you're looking to size a
temperature control valve on the steam inlet to maintain a given
temperature on whatever it is you're heating. This means that the
temperature control valve will throttle the steam flow based on the temp
it senses. At lower loads, this will give you the same effect as a
pressure reducing valve. As the TCV throttles-in, the steam pressure in
the HX will fall. You need to select a steam trap with this in mind, and
make sure that the condensate can drain by gravity from the HX.
Companies like Spirax Sarco, Armstrong, etc can help you with this
application