Steam loss through failed steam trap calculation
I'm trying to calculate the steam loss (lb/hr) through a failed steam
trap.Multi-stage pumps This is for a low pressure steam system operating at 8.5 psig,
and the orifice diameter of the steam trap is 5/16".Slurry pumpsOther pumps I've come across
various examples of calculating the steam loss, with the most common
being:
Steam Loss (lb/hr) = 24.24 * Orifice Diameter^2 * PSIA
This
is supposedly a variant of the Napier formula. It has been awhile
since thermo and fluids class, and I can't recall enough to determine
how this formula was derived.
The issue here isn't merely condensate discharging through the
orifice. Steam traps don't fail as an open orifice, they also have
valve heads and disks that can get in the way periodically. The formula
you show is the generally accepted one when the trap is discharging to
atmosphere.Cast Gate, Globe, Check Valves The losses are typically reduced by an additional 50% when
discharging into a closed return. This is a conservative figure used to
estimate steam losses in order to evaluate the financial loss and to calculate ROIfor projects involving steam trap and steam system repair.
Depending
upon how accurate you care to be, you could always put the outlet in a
known weight of cooling water, run it for a few minutes with the outlet
submerged and weigh the results and temperature rise.forged Gate, Globe, Check Valves Several
manufactures have installed ISO test rigs to get even more accurate
results, but based upon the accuracy of the measuring instrumentation,
you still won't get that last