Spill back control valve for capacity control
Refer to API 618 capacity of reciprocating compressors could be
controlled by unloading device, clearance pocket and spillback control
valve.
If five steps unloading (i.e. 0, 25, 50, 75 and 100% of full
flow) are used in combination of spillback control valve, it is kindly
requested to inform us about following questions,
1. Which flows are reported as maximum, normal and minimum flow for control valve sizing?
2. Is it necessary to report full flow of compressor as a shutdown case for this valve and consider it to CV calculation?
3. If the response to item 2 is yes ,so which DP will be considered for valve in settle out (shut down)case?
1. Difference between system design flow conditions and compressor flow
capability will dictate what the flow requirements are for the
valve. For instance, station operating flow condition is desired to be
200 MMSCFD and compressor unloading and speed control can only achieve a
minimum of 250 MMSCFD at those conditions, then 50 MMSCFD at the stated
suction and discharge pressures will be one point of consideration.
2.
Depends on the installation. For stations with larger units, say more
than 1500 hp each. there generally is a unit bypass valve used for
compressor start up and shutdown. The station recycle or "spillback"
valve is a seperate valve used only for flow control.
For
stations with small units, say <1500 hp...you sometimes can combine
the spill back and unit bypass valve into the same valve and generally
will not be a globe type control valve, it should be a ball type control
valve, and thus it needs to be sized for shutdown operation, for which
there's no real cut and dry way of sizing. you'll have to look at your
conditions to determine if this method is feasible...i.e. look at
discharge temperatures with the spill back valve open, is there enough
gas cooling, does the spill back valve need to tie in further upstream
of the compressor.
To size the bypass valve, first you'll need to determine what the
compressor flow capacity is with a small differential say 50 psid or
so. Then use this flow and d/p to determine what size valve you may
need. (FYI, plug valves work well as a bypass valve). You should play
with the valve size, flow, d/p, and unit horsepwer to get the best valve
fit. It's desirable to have a little bit of parasitic gas load when
starting the unit.
Chances are that your bypass valve will need
to be larger than your spillback valve, in which case the valve should
be in parallel.
You may be able to use a single larger control
valve to serve both functions, such that the spill back control range of
the valve is more at the closed end of the valve say 0 to 30% open
versus 0 to 80% open, however you may have issues tuning the controls
for steady state or transient operation.
MORE NEWS